Model
DPL110

Dual Point Level Switch
Tank High/Low Control, Conductivity Technology, Up to 72" Probe

SPECIFICATIONS
Electrodes: 1/8" dia, 24" (609.6 mm) length, standard.
Wetted Materials: 316 Stainless Steel, polypropylene.
Mounting, Sensor Head: 1" male NPT.
Pressure Limits: 30 psig (2.06 bar).
Temperature Limits: 212°F (100°C).
Probe Enclosure: NEMA 6 (IP67).
Maximum Probe Length: 72" (1.8 m) with optional extensions.
Connecting Cable, Probe to Controller: 10 ft (3.0 m).
Sensing Voltage: 12 VAC.
Power Supply: 120 VAC 50/60 Hz.
Output: SPDT, 5A @ 240 VAC.
Mounting, Controller: Standard octal socket or 35 mm DIN rail.
Weight, Probe Assembly: 1.5 lb (0.68 kg).
Weight, Controller: 1.0 lb (0.45 kg).