FPC-1200

Duplex Pump Controller
Full-Featured, Low-Cost

SPECIFICATIONS
Inputs: Floats: Open circuit voltage: 5 VDC; Short circuit current: 2 mA maximum. Auxiliary motor starter contacts: Open circuit voltage: 12 VDC; Short circuit current: 2 mA maximum. Temperature and seal failure: Open circuit voltage: 5 VDC; Short circuit current: 2 mA maximum. Mute: Open circuit voltage: 5 VDC; Short circuit current: 2 mA maximum.
Output Type: (2) Form A SPST contacts for pump output, (1) Form A SPST contact for seal-fail alarm, (2) 12 VDC driver outputs for High Alarm horn and light.
Output Ratings: Form A SPST: 5 A @ 120 VAC; 12 VDC driver: 100 mA @ 12 VDC.
Control Type: On/off pump out (down).
Power Requirements: 120 VAC ± 15%, 50 to 70 Hz.
Power Consumption: .25 A @ 120 VAC.
Temperature Limits: -4 to 140°F (-20 to 60°C).
Seal Failure (Moisture Sensor): Trip point: 50,000 Ohms.
Weight: 1 lb 4 oz (454 g).
Agency Approvals: UL pending.