FEATURES
- Selectable pump alternation when used with two pumps to minimize
pump wear. With alternation “on” a seal failure or over temperature
condition will force the non-failed pump to lead status and stop
alternation.
- When used with a submersible pump including a moisture sensor the
MPC has alarm light indication of seal failure.
- When used with a pump including a thermostat the MPC has alarm
light indication of pump over temperature and removes the pump from
service. The Pump can be brought back into service automatically
or by manual reset when the pump has cooled down.
- Alarms can be programmed for output indication of pump seal failure
or over temperature.
- Selectable time delay, for pump two, on power up to prevent both
pumps from starting at the same time. If power is lost, upon regaining
power a time delay of up to 60 seconds can be selected to prevent
too large of a current draw.
- Integral 24 VDC power supply for level transmitter.
- Displays pump run time from a front panel button.
- Test System function that simulates the process input to insure
the pumps are operating or to test programming.
- User selectable security lock-out of programming and/or set points.
- Process input retransmission as a current (4 to 20 mA) or voltage
(2 to 10 VDC) analog signal*.
* Standard model MPC is set for current retransmission. For voltage retransmission
add suffix “-RV”.
|