Home Product Information Free Literature International Distribution What's New About Us Contact Us
New Quick Search Order Form
Dwyer Series
608

Differential Pressure Transmitter
Ranges Down to 0.1" w.c., Intrinsically Safe, NEMA 4X

SPECIFICATIONS
Service: Clean/dry air and compatible combustible gases (see Agency Approvals for FM ratings).
Wetted Materials: Consult factory.
Accuracy: ±0.5% or ±0.25% full scale.
Stability: ±0.5% F.S./yr.
Pressure Limits: 100 psig (6.89 bar); 15 psid (1.03 bar).
Temperature Limits:
-20 to 185°F (-28 to 85°C).
Compensated Temperature Range: 0 to 160°F (-18 to 71°C).
Thermal Effect: 0.5% Accuracy: ±0.02% F.S./°F; 0.25% Accuracy: ±0.01% F.S./°F.
Power Requirements: 12 to 36 VDC (2-wire).
Output Signal: 4 to 20 mA DC.
Zero and Span Adjustments: Potentiometers for zero and span.
Response Time: 250 ms.
Loop Resistance: DC: 0-1045 ohms maximum.
Current Consumption: 4-20 mA.
Electrical Connections: Screw terminals: two 1/2" female NPT conduit.
Process Connections: Two 1/4" female NPT.
Enclosure Rating: NEMA 4X (IP65).
Mounting Orientation: Not position sensitive.
Weight: 2 lb (0.9 kg).
Agency Approvals: FM approved intrinsically safe for use in Class I, Div. 1, Groups A, B, C, D; Class II, Div. 1, Groups E, F, G; Class III, Div. 1 when wire with approved intrinsically safe barrier. Entity parameters: Vmax=36 VDC; Imax=250 mA; C=12 nF; L=0 mH.