Home Product Information Free Literature International Distribution What's New About Us Contact Us
New Quick Search Order Form
Mineral Insulated Thermocouples and RTDs
Mineral Insulated Thermocouples and RTDs are known for their excellent mechanical durability and resistance to electrical breakdown. Available in outside diameters from 0.020 inch (0.5 mm) to 0.500 inch (12.7 mm), Mineral Insulated Thermocouples can be bent to most any angle without special equipment. Because of its flexibility, the mineral insulated material can be made to extremely long lengths, coiled for inexpensive shipment, and straightened upon arrival without damage.

Ungrounded and exposed junctions are electronically isolated from the sheath. Minimum resistance is 1.5 megohms at 500 VDC.

Due to the varying sized of connection wire and cable, a transition fitting is used between the cold end of the sheath and the connecting wires. This fitting measures 1-1/4" long by 1/4" outside diameter for 1/8" or smaller sheaths, and 1-1/2" long by 3/8" outside diameter for 3/16" and 1/4" sheaths. Larger sheaths are usually connected to bushings or connector heads, and usually do not require transition fittings. Sheaths terminating connectors other than wire or cable do not require transition fittings.

Home
Product Information
Free Literature
International Distribution
About Us
Contact Us
Terms & Conditions of Sale
Terms of Access
© Copyright 2005  Dwyer Instruments Ltd. All rights reserved.