SPECIFICATIONS
Inputs: Thermocouple (J type stocked), field selectable K, T,
E, or N type; RTD (100Ω DIN).
Display: 4 digit, 7 segment 0.3" high LED display; Set Point
and Alarm status LED indicators; °F or °C LED indicators.
Accuracy: ±0.25% of span ±1 least significant
digit.
Supply Voltage: 100 to 240 VAC, 50 to 400 Hz. single phase;
132 to 240 VDC (nom.) +10% - 20%. 5 VA maximum power consumption.
Temperature Range: Operating 14 to 131°F
(-10 to 55°C);
storage -40 to176°F (-40 to 80°C).
Output Ratings: SSR: 3.5A @ 240 VAC max. @ 77° (25°C)
typical. Relay (SPST): 3A res., 1.5A ind. @ 250 VAC; Pilot Duty = 250
VA, 2A @ 125 VAC or 1A @ 250 VAC.
Alarm Rating (optional): Relay (SPST): 3A res., 1.5A ind. @
250 VAC.
Isolation: Relay and SSR outputs are isolated.
Sensor Break Protection: De-energizes control output.
Weight: 8 oz (227 g).
Front Panel Rating: NEMA 4X (IP65). |