SPECIFICATIONS
Probe Range: 0 to 700°C (32 to 999°F) for thermocouple
J, 0 to 999°C (32 to 999°F) for thermocouple K,S.
Input: Type J or K thermocouple.
Output: 15 A SPDT relay @ 250 VAC resistive.
Horsepower Rating (HP): 3/4 HP.
Control Type: ON/OFF.
Power Requirements: 110 VAC, 230 VAC, 12 VAC/VDC, or 24 VAC/VDC(depending
on model).
Accuracy: ±1% FS.
Display: 3-digit, red, 1/2" (12.7 mm) digits, plus sign.
Resolution: 1°.
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 14 to 158°F (-10 to 70°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: IP64..
Agency Approvals: CE, UR, URc.
PARAMETERS
|
|
Description
|
Units
|
Range
|
SP
|
Set Point
|
Degrees
|
r1 to r2
|
r0
|
Differential or Hysteresis
|
Degrees
|
1 to 99°
|
r1
|
Lower Value Set Point
|
Degrees
|
0 to 999°
|
r2
|
Higher Value Set Point
|
Degrees
|
0 to 999°
|
d0
|
Heating or Cooling Control
|
Option
|
Ht/Co
|
c0
|
Min. Stop Time for Load
|
Minutes
|
0 to 59 min.
|
c2
|
Load Status During Probe
Error
|
0/1
|
Off/On
|
P1
|
Ambient Probe Adjustment
|
Degrees
|
-10 to 10
|
P5
|
Ambient Probe Type
|
Option
|
J, K, or S
|
H5
|
Parameter Access Code
|
Numeric
|
0 to 255 (Set at 0 from factory)
|
A0
|
Alarm 1 Hysteresis
|
Degrees
|
1 to 999°
|
A1
|
Alarm 1 Threshold
|
Degrees
|
0 to 999°
|
A2
|
Alarm 1 Exclusion Time
|
Seconds
|
0 to 999
|
A3
|
Alarm 1 Configuration
|
Option
|
Off, 1, or 2
|
A4
|
Alarm 2 Hysteresis
|
Degrees
|
1 to 999°
|
A5
|
Alarm 2 Threshold
|
Degrees
|
0 to 999°
|
A6
|
Alarm 2 Exclusion
|
Seconds
|
0 to 999
|
A7
|
Alarm 2 Configuration
|
Option
|
Off, 1, or 2
|
|