SPECIFICATIONS
Probe range: PTC: -58 to 302°F (-50 to 150°C); NTC:
-58 to 230°F (-50 to 110°C).
Input: PTC/NTC thermistor (1000 Ω @
25°C).
Output: 16A SPST relay @ 250 VAC resistive, 5A inductive;
dual output units also have one 8A SPDT relay @ 240 VAC resistive,
3A inductive.
Horsepower Rating (HP): 16A: 1 HP 240 VAC - 10 FLA, 60 LRA
250 VAC.
Control Type: ON/OFF.
Power Requirements: 110 VAC; 230 VAC; 24 VAC/DC; 12
VAC/VDC (depending on model).
Accuracy: ±1% F.S.
Display: 3-digit, red, 1/2" (12.7 mm) digits.
Resolution: 0.1° (<100°); 1° (≥100°).
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 14 to 131°F (-10 to
55°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: IP64.
Agency Approvals: UR pending.
PARAMETERS
|
|
Description
|
Units
|
Range
|
SP
|
Set point
|
Degrees
|
r1 to r2
|
r0
|
Differential or Hysteresis
|
Degrees
|
1 to 20
|
r1
|
Lower Value for SP
|
Degrees
|
-48 to r2
|
r2
|
Higher Value for SP
|
Degrees
|
r1 to 302
|
d0
|
Type of Defrosting
|
Option
|
rE/ln
|
d1
|
Temperature Defrosting Stop
|
Degrees
|
-58 to 302
|
d2
|
Defrosting Duration
|
Minutes
|
0 to 59
|
d4
|
Delay of First Defrosting
|
Minutes
|
0 to 999
|
d5
|
Display on Defrosting
|
Option
|
off/on/-d-
|
d7
|
Compressor Drip Time
|
Minutes
|
0 to 999
|
d8
|
Defrosting Interval Time
|
Hours
|
0 to 24
|
d14
|
Defrost Counting Mode
|
Option
|
ct/rt
|
c0
|
Minimum Stopping Time
|
Minutes
|
0 to 59
|
c2
|
ON Time of Fault Cycle
|
Minutes
|
0 to 999
|
c3
|
OFF Time of Fault Cycle
|
Minutes
|
0 to 999
|
c4
|
Minimum ON Time
|
Minutes
|
0 to 999
|
c5
|
Minimum Time Between
2 Activations
|
Minutes
|
0 to 999
|
P1
| Ambient Probe Adjustment
|
Degrees
|
-10 to 10
|
P2
|
Defrosting Probe Adjustment
|
Degrees
|
-10 to 10
|
P4
|
Number of Probes
|
Option
|
1/2
|
H1
|
Keyboard Protection
|
Minutes
|
yes/no
|
H5
|
Access Code to Parameters
|
Numeric
|
0 to 255
|
H6
|
Probe Type
|
Option
|
ptc/ntc
|
|