SPECIFICATIONS
Power Requirements: 24 VAC, ±10%, 50/60 Hz, single phase.
Power Consumption: 4 VA.
Control Input: 4-20 mA or 0-10 VDC.
Overload Protection: Magnetic clutch.
Angle of Rotation: 95° (mechanically adjustable).
Accuracy: +/- 5%.
Fits Shaft Diameter: 0.4” (10 mm) or 0.5” (13 mm).
Position Indication: Visual indicator.
Direction of Rotation: CW/CCW.
Running Time: 17 in-lb, 35 in-lb, 53 in-lb: 110 sec.; 70 in-lb: 160 sec.
Electrical Connection: Terminal block, 18 AWG.
Manual Override: Push button.
Temperature Limit: -22 to 122°F (-30 to 50°C).
Sound: <45 dB.
Life Expectancy: 60000 full cycles.
Housing: NEMA 2 (IP40).
Wiring Connection: Terminal block.
Standard Accessories: (2) imitative baffles, (2) baffle setscrews, (1) actuator body setscrew, and (1) aluminum gasket.
Weight: 1.72 lb (0.78 kg).