Series
EPT-1
Electro-pneumatic Transducer
Low Cost, Selectable Input, Manual Override

SPECIFICATIONS
Service: Clean dry air or any inert gas.
Input Signal:
DC Current (4-20 mA) or DC Voltage (0-5/0-10).
Input Impedance:
Current: 301 ohms; Voltage: 10K ohms.
Air Supply: 40 psig (276 kPa) maximum.
Accuracy: ±1% F.S. (includes linearity, hysteresis and repeatability).
Pressure Drop: (Supply to branch) 0.1 psig (0.7 kPa).
Power Requirement: 18-28 VAC/VDC.
Current Consumption: 150 mA.
Temperature Limits: 25 to 150°F (4 to 65°C).
Thermal Effect: ±0.025%/°F (0.03%/°C).
Pressure Connections: 1/4" O.D. plastic tubing.
Electrical Connections: Screw terminals.
Wire Size: 12 Ga max.
Enclosure: 18 Ga C.R. steel chassis with baked on enamel PMS2GR88B finish.
Weight: 1.0 lb (0.45 kg).